Til toppen

Pulse Train Output (PTO) modul

Produktnummer: 5034-PTO-AM
 

inkl. mva.

5034-PTO-AM er en pulse train output-modul utviklet for Rockwell Automation sin PointMax™ I/O-plattform. Den leverer høyhastighets pulsutgang for styring av stepper- og servo-drivere, med valgbare signalformater: Step & Direction eller CW/CCW.

Modulen støtter encoder-feedback (inkrementell og SSI), har fire programmerbare innganger og en dedikert 24 V hjelpeutgang. Med tilgjengelig Add-On Profile forenkles integrasjonen i Rockwell-baserte systemer via Studio 5000.

 

I/O and Feedback Capabilities

AMCI Module 5034-PTO-AM
PLC platform PointMax I/O
Number of channels     (1) channel
Encoder inputs -Quadrature (X4 decode), up to 250 kHz
-Differential input, 10 mA @ 5 Vdc
-SSI absolute encoder interface
Inputs (x4) -2x fast inputs (8–30 Vdc, 1µs response)
-2x slow inputs (3.5–30 Vdc)
-Input Current: 15 mA @ 24 Vdc
-Assignable for general-purpose use, limits, capture, or registration

Electrical

AMCI Module 5034-PTO-AM
Backplane current draw      2W max
Pulse output Differential, 5 Vdc, 20 mA max per output
Frequency range 1 Hz to 1 MHz, programmable in 1 Hz steps
Power output -24 Vdc, programmable
-0.5 to 1 A
-Protected
-Can power encoders or other devices

Inputs

AMCI Module 5034-PTO-AM
Input type Sinking
Fast inputs 8–30 Vdc, 1µs
Slow inputs 3.5–30 Vdc
Input Current 15 mA @ 24 Vdc
Programmability    User-defined function per input

Environmental

AMCI Module 5034-PTO-AM
Operating temperature    32°F to 140°F (0°C to 60°C)
Storage temperature -40°F to +185°F (-40°C to +85°C)
Relative humidity 5% to 95%, non-condensing


Required equipment: 5034-RTB18 (screw clamp) or the 5034-RTB18S (spring clamp) mounting base assembly. These parts must be separately ordered from Rockwell Automation.

5034 Mounting Base 15mm

5034-MB
 

5034 RTB Spring w. Pusher 18 Terminals

5034-RTB18S
 

2-channel pulse-width modulation by AMCI

Modul for distribuert PWM-kontroll direkte i PointMax I/O-rack. Kompatibel med Rockwell Automation PointMax™ 5034 I/O-system og programmerbar via Logix (Studio 5000).
5034-PWM-AM
 

5034 Ethernet/IP RJ45 Adapter

5034-AENTR