To top

LonWorks to EtherNet/IP, BACnet/IP, Modbus/TCP and Modbus RT

SKU: PS-QS-1211-F
 

incl. VAT

BACnet/IP, EtherNet/IP Modbus TCP/IP and Modbus® RTU to LonWorks - 500 points

The QuickServer line of communication gateways are designed to link building automation networks utilizing LonWorks with industrial control networks communicating on BACnet/IP, EtherNet/IP, Modbus TCP/IP, and Modbus RTU. The QuickServer gateways are available with limits of up to 250 or 500 points of application data.

PS-QS-1011-F  supports 500 Points

The gateway is challenging to configure and will require editing the configuration file using spreadsheet programs or any text editor. The configuration file is comma-delimited format (*.csv) where entries within a line are separated by commas and the end of a line is indicated by an entry without a comma. 

Documentation and Downloads

Features and Benefits

  • Ability to interface up to 250 or 500 points of common BAS protocols depending on gateway
  • Multi-configuration capability; specific configurations selectable via DIP switches or software
  • DIN rail mount included with gateway
  • DIP switches to select baud rate or node ID on the fly
  • BACnet COV support for fast data communication while reducing the traffic over a BACnet network. BTL Marked (PS-QS-1X10-XXXX) and LonMark Certified (PS-QS-1X11-XXXX)

Specifications

Field Connections

  • Ethernet 10/100 RJ45
  • Serial RS-485 terminal (up to 115K baud)
  • FTT-10 LonWorks port

Other

  • Configuration/Diagnostic utilities
  • Capacity: 250 or 500 Points
  • Table, Wall or DIN rail mount

Approvals

  • TUV approved to UL 916 standard
  • CE Mark
  • BTL Mark (PS-QS-1010)
  • RoHS Compliant
  • FCC Part 15 Compliant

Hardware

Environment

  • Operating temperature: -40°F to 167°F (-40°C to 75°C)
  • Relative humidity: 5% to 90% RH, with no condensation

Power Requirements

  • 9 to 30 Vdc or Vac or 5 Vdc
  • Current draw 250mA @ 12V

Physical Dimensions 

  • W x D x H: 11.5 x 8.3 x 4.1 cm
  • 0.2 Kg