Til toppen
Produktet er ikke aktivt!

IXXAT SG-gateway with PROFINET + IEC61850 incl. SD-card

Produktnummer: ASG4004-C

ASG4004-C - SG-gateway with PROFINET - supporting IEC61850 client/server

SG-gateway with PROFINET

Bridging the gap between industrial and energy communication

The SG-gateway supports the communication protocols used in the energy sector, including IEC60870-5-104, DNP3 and IEC61850 and enables connectivity for energy devices to PROFINET-based automation systems. On top of that the simultaneously usable OPC-UA and MQTT functionality empower direct integration into the companies’ cloud-based applications.

The PROFINET interface for Siemens-PLCs implements an isochronous real-time PROFINET device interface with an integrated 2-port switch, allowing seamless network integration regardless of network topology.

In addition to PROFINET, IEC and DNP3 protocols, other electric equipment in the field can also be connected via Modbus-TCP and RTU. As an option, the SG-gateway can also include a 3G modem for remote connectivity.

 

FEATURES AND BENEFITS

  • Connects intelligent electrical devices (IEDs) with IEC or DNP3 protocols to industrial automation PLC systems using PROFINET or Modbus.
  • Easy way to transport I/O data from electrical equipment in the field to SCADA systems
  • Connects industrial machines to energy SCADA systems
  • Connects switchgear to industrial PLCs
  • Supports several communication protocols (IEC61850, IEC60870-5-104, DNP3, Modbus, OPC-UA, MQTT)
  • Connectivity via Ethernet or via optional 3G modem
  • Easy web-based configuration using any standard browser
  • Onboard WebPLC for easy data conversion and control functions
  • Robust metal housing for stand-alone operation with DIN rail mounting
  • Global technical support and consulting services
  • Range of cybersecurity features including password protection, user management, and OpenVPN
  • Continuous software maintenance by HMS, devices can be upgraded in the field
  • Easy export and import of configuration to ease volume installations

 

PROFINET INTERFACE

  • PROFINET-IO Real-Time (RT) Class 1 & 3 communication V 2.31
  • Max 1440 bytes of Input and 1440 bytes of Output data
  • Up to 128 modules
  • Baud rate 100 Mbit/s fixed
  • SNMP-MIBII support
  • Generic and PROFINET specific diagnostic support
  • Supports PROFIenergy profile
  • Supports Media Redundancy Protocol (MRP)
  • Device identity customization
  • Supports PROFINET Fast Start Up
  • PROFINET uplink configuration via GSDML file
  • Integrated IRT switch enabling a daisy-chain topology
  • Dual RJ-45 network ports available simultaneously

 

ADDITIONAL INTERFACES

ETHERNET INTERFACE

  • 10/100 Mbit/s
  • DHCP server
  • SNTP
  • NAT routing
  • SNMP manager

 

SERIAL INTERFACE

  • Selectable RS-232/485
  • Serial baud rate 300 bps - 187,5 kbps

 

SECURITY FEATURES

  • OpenVPN client
  • TLS data encryption
  • Integrated Firewall
  • Password protection with password policy
  • Support for user roles
  • Root access authentication
  • Usage of standard ports for easy integration into firewalled environments

 

MODBUS/TCP

  • Supports Modbus TCP Client/Server
  • Connects up to 128 server devices and supports 4096 values

 

MODBUS RTU

  • Supports Modbus RTU Master/Slave
  • Connects up to 128 serial Modbus RTU slave devices and supports up to 4096 values

 

DNP3 (OPTIONAL)

  • Outstation: 1 TCP link, up to 4 local/master links
  • Up to 4096 data objects (each data object with value, quality and timestamp)

 

IEC61850

  • Client/Server
  • Goose Publisher/Subscriber
  • Up to 4096 data objects (each data object with value, quality and timestamp)
  • 32 server devices supported in Client configuration

 

IEC60870-5-104 (OPTIONAL)

  • Client/Server functionality
  • Up to 4096 data objects (each data object with value, quality and timestamp)
  • 32 server devices supported in Client configuration
  • Support for IEC60870-5-104 redundancy according to Norwegian User Convention

 

WIRELESS MODEM (OPTIONAL)

  • SMS Send and Receive
  • Telecontrol access to the control room communicating IEC60870-5-104 or IEC61850 remote telecontrol protocols
  • GSM/GPRS Quad band 850/900/1800/1900 MHz
  • UMTS Seven band: 800/850/900/AWS 1700/1900/2100 MHz
  • Mini SIM (2FF)
  • For LTE/4G or NBIOT support, please contact HMS sales

 

OPC-UA

  • Micro Embedded Device Server Profile
  • UA-TCP, UA-SC, UA-Binary protocol and encoding
  • Up to 128 groups, 4096 values
  • Up to 4 concurrent client sessions

 

MQTT

  • Client version 3.1 and 3.11
  • Flexible for own definition of payloads
  • Last will, QoS, Keep alive interval
  • TLS encryption